BS 6622 Three Core Armoured 15KV XLPE Stranded Copper Conductors
Construction
| cross-sectional area mmsq  | Minimum average thickness of insulation mm  | Nominal diameter over insulation  
 | Nominal thickness of PVC bedding mm | Nominal number and diameter of armoured wires no./mm | Nominal thickness of PVC oversheath mm | Nominal overall diameter of cable mm  | 
| 50 | 4.5 | 19.4 | 1.5 | 56/2.5 | 2.8 | 58.8 | 
| 70 | 4.5 | 21.2 | 1.5 | 60/2.5 | 2.9 | 62.9 | 
| 95 | 4.5 | 22.9 | 1.6 | 65/2.5 | 3.0 | 67.0 | 
| 120 | 4.5 | 24.4 | 1.7 | 68/2.5 | 3.1 | 70.6 | 
| 150 | 4.5 | 25.7 | 1.7 | 71/2.5 | 3.2 | 73.6 | 
| 185 | 4.5 | 27.5 | 1.8 | 61/3.15 | 3.4 | 79.4 | 
| 240 | 4.5 | 29.7 | 1.9 | 65/3.15 | 3.6 | 84.7 | 
| 300 | 4.5 | 32.0 | 2.0 | 70/3.15 | 3.7 | 90.1 | 
| 400 | 4.5 | 34.7 | 2.1 | 75/3.15 | 4.0 | 96.7 | 
Installation
| cross-sectional area mmsq  | Approximate cable weight kg/m | Nominal drum length  m | Minimum bending radius mm  | Nominal  internal diameter of ducts mm  | 
| 50 | 6.1 | 500 | 900 | 100 | 
| 70 | 7.1 | 500 | 950 | 100 | 
| 95 | 8.3 | 500 | 1050 | 125 | 
| 120 | 9.4 | 500 | 1100 | 125 | 
| 150 | 10.5 | 450 | 1150 | 125 | 
| 185 | 12.9 | 400 | 1200 | 125 | 
| 240 | 15.2 | 350 | 1300 | 125 | 
| 300 | 17.6 | 300 | 1400 | 125 | 
| 400 | 20.8 | 250 | 1500 | 125 | 
Electrical Performance
| cross-sectional area mmsq  | Maximum DC resistance of conductor at 20 
    
     ℃
    
uohms/m  | Maximum AC resistance of conductor at 90 ℃ uohms/m  | Reactance at 50Hz  uohms/m | Impedance at 50Hz uohms/m  | Maximum Capacitace PF/m  | Maximum charging current at normal voltage and frequency mA/m  | 
| 50 | 387 | 494 | 123 | 508 | 211 | 0.58 | 
| 70 | 268 | 343 | 115 | 361 | 240 | 0.65 | 
| 95 | 193 | 248 | 109 | 270 | 267 | 0.73 | 
| 120 | 153 | 196 | 105 | 223 | 291 | 0.79 | 
| 150 | 124 | 159 | 102 | 189 | 312 | 0.85 | 
| 185 | 99.1 | 128 | 98.6 | 162 | 340 | 0.93 | 
| 240 | 75.4 | 98 | 95.2 | 137 | 375 | 1.02 | 
| 300 | 60.1 | 80 | 92.2 | 123 | 411 | 1.12 | 
| 400 | 47 | 64 | 89.3 | 110 | 454 | 1.24 | 
Ratings
| Cross-sectional area  mmsq | Current Ratings  | Short circuit ratings  | |||
| Laid direct in ground Amps | Drawn into ducts Amps | Laid in air Amps | One second short circuit rating of conductor KA | One second short circuit rating of copper per core KA | |
| 50 | 210 | 180 | 220 | 6.8 | Typically less then 1kA | 
| 70 | 255 | 215 | 270 | 9.8 | |
| 95 | 300 | 255 | 330 | 13.3 | |
| 120 | 340 | 290 | 375 | 17.2 | |
| 150 | 380 | 330 | 430 | 21.2 | |
| 185 | 430 | 370 | 490 | 26.6 | |
| 240 | 490 | 425 | 570 | 34.9 | |
| 300 | 540 | 470 | 650 | 43.8 | |
| 400 | 590 | 520 | 700 | 57.3 | |